Part Number: ETI0001-1444 NSN:
6130-01-511-6232
Rugged
MilSpec 2000VA Integrated
Rackmount UPS and Intelligent
Power Distribution Unit Combination
Boeing / Navy Rugged MilSpecStandard Product PowerStationÔ
Isolated N5 UPS Configuration
Ultra Quiet 2000 VA Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
ETI0001-1444 Rugged MilSpec UPS and PDU Standard Front Panel Layout
ETI0001-1444 Rugged MilSpec UPS and PDU Standard Rear Panel Layout
Optional P/N: ETI0001-0876 UPS and PDU Remote Control Panel in 1U
The field proven PowerStation™ UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.
These units are equally suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled environments.
The ETI0001-1444 was specifically designed to meet the stringent
requirements of Boeing for use in multiple programs.
The ETI0001-1444 does not require a separate PDU since the PDU
functions are already integrated into the UPS module. This saves rack space, cabling and
expense while improving overall reliability.
The heavy-duty chassis occupies only 3U (5.25”) of
rack space while delivering up to 2000 VA of clean, uninterruptible power. The front panel is sealed meeting the Navy drip proof
requirements. The
rounded metal corners and rugged handles, both front and rear, aid in safe
handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration in any axis.
The internal shielded
input transformer provides galvanic isolation with provisions for both domestic
(115 VAC, CONUS) and optional autoranging international input voltages (85-270 VAC,
OCONUS).
The
unit also operates as a frequency converter, taking 46-70 hertz input and
converting it to 60 hertz power.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for shipboard systems or
overseas locations where phase references and grounding are not consistent.
The LED
arrays keep the operator informed as to the unit's status including load and
battery levels. The Elapsed
Time Indicator records the number of operational hours for records and
scheduling preventative maintenance of attached equipment. The
high intensity audible alarm can be heard in high noise environments and
includes an audible enable/disable switch. All controls
and protective devices are brought to the front and rear panels with critical switches or
breakers guarded. Further, all front panel devices are recessed to prevent
damage or accidental operation.
The internal intelligent PDU allows control of
the individual output circuits incorporating thermal and interlock interfaces
for additional control and safety, plus Battleshort override. Battleshort can be
engaged via the front panel control to override thermal shutdown. When in
Battleshort, an audible alarm is sounded and an indicator is lit. The display and
control panel can be mounted remotely in the rack at eye level, or on the keyboard console,
or on the unit front panel with only a logic level cable connection.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. The output connectors are unique MS threaded metal shell connectors,
each "clocked" differently so only one cable can go to each output. This
unit draws air through the side air vents and exhausts out the rear vent into the rack.
This allows the unit to be used in either positive, negative or neutral pressure
racks. The fan is a special extra quiet version to keep the unit's overall
audible level below 44 dB.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. The
Status connector provides an
interface with optional computer software providing loss of AC and low battery status as well as
remote shut down capability. The UPS Remote Control and PDU Remote Control connectors provide an
interface to optional remote display/control panels.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series for a
version of UPS without the integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical shipboard,
vehicle, airborne or land based systems combining advanced modular design
features with highly reliable construction.
Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS
110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS
Less than 5.0% into 100% non-linear load
Output frequency: UPS
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available 400 or 1000 Hz
output available as an option
Operational status
AC Input status, UPS operational,
UPS alarm, Battery level, Low battery, Load level, Overload, Warm
temperature, Hot temperature and Battleshort LEDs, Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
85 dB audible alarm with audible on/off switch
AC INPUT
Input voltage selection:
Nominal 115 VAC,
Optional
autoranging input of 85-270 VAC
Input voltage tolerance: UPS
85-135 VAC @ full load without
using battery,
Down to 70 VAC @ 75% load
Input frequency:
From 46 Hz to 70 Hz standard,
optional to 440 Hz
Input power factor:
Better than 99% typically
Input/output isolation:
2000 VA, up to 120 dB common mode,
<1.0 mA leakage
Input transient suppression:
Complies with IEEE 587, UL 1449 and
Mil Std 1399
Input control/protection:
Guarded 2 pole 100 G shock rated
circuit breaker (CB1)
plus UPS input fuse (F2),
spare fuse on front
Optional cold start to turn on w/o AC present